In the service of the built  environment.


Specifications


Relative Humidity Controller

The relative humidity controller shall be microprocessor based.

For general application, it shall use a high polymer type sensor with a range of 30-80% and accuracy 5% of relative humidity.

For critical applications, the sensor used shall be capacitive type with a range of 0-100% and accuracy of 3% of relative humidity.

For ON/OFF application the controller shall have a changeover contact of 230V, 3 Amp rating.

For modulating application, the output shall be 3 point or 0-10 VDC.