Support  |  Technical Notes  |  Order & Delivery  |  Anergy World  |  Corporate  |  R&D  |  Media File  |  Contact Us |  Home  | Back

 


Select product


   Rotary Actuators

SMU-24(-S/-F/-T)




  Dimensions
  Wiring diagram

  SMU24-SR

 TECHNICAL DATA

Electrical data  
Nominal Voltage AC 24 V 50/60 HZ, DC 24 V
Nominal Voltage Range AC/DC 19.2 ...28.8 V
Power consumption 2 W @ running/0.2 W @ holding
Wire Sizing 4 VA
Max. peak current 2.7 A @ 5 ms
Auxiliary switch SMU24-S 1 SPDT,1 mA ...3(0.5)A, AC 250 V, adjustable
Connection: Motor Cable 1 m, 3 x 0.75 mm2
Auxiliary switch (SMU24-S) Cable 1 m, 3 x 0.75 mm2
Terminals SMU24-T max. 3 x 1.5 mm2
Functional data  
Torque 20 Nm
Direction of rotation Selectable by switch
Manual operation Gearing disengaged by pressing the pushbutton, manual operate while the button is held depressed.
Angle of rotation max. 95o,adjustable by mechanical stops
Running time 150 s for 95o
Sound power level max. 45dB (A)
Position indication mechanical, remote visible
Working conditions  
Protection Class III(safety low voltage)
Degree of protection : SMU24(-S/F)
                                SMU24-T
IP54 in any direction
IP20
EMC CE according to 89/336/EEC
Mode of operation Type 1 to EN 60730-1
Ambient temperature -30... +50oC
Non-operating temperature -40... +80oC
Humidity test 95% RH, non condensing(EN 60730-1)
Maintenance maintenance free
Dimensions / weight  
Dimensions(L x W x H) See 'Dimensions'
Shaft length min, 42 mm (20mm with K-SA)
Shaft:SMU24(-T/S)
         SMU24-F
min, 10...20 mm (10...26.7 mm with K-ENSA)
12 x 12 mm
Weight approx. 1050 g

Anergy Instruments Pvt. Ltd., 40, Sector - 27 A, Faridabad - 121 003, India    Tel 91-129-4045901 - 3, 2276589    Fax 91-129-2276482  